Sorry, you need to enable JavaScript to visit this website.

doee

DOEE
Menu

Proposed Air Quality Permit 7165 - Adams Morgan Hotel Owner

Friday, February 10, 2017

PUBLIC NOTICE

Proposed Air Quality Permit 7165, Adams Morgan Hotel Owner LLC, Construction and operation of one 505 kWe diesel-fired emergency generator set at 1770 Euclid Street NW

Notice is hereby given that, pursuant to 40 C.F.R. Part 51.161, D.C. Official Code §2-505, and 20 DCMR § 210, the Air Quality Division (AQD) of the Department of Energy and Environment (DOEE), located at 1200 First Street NE, 5th Floor, Washington, DC, intends to issue air quality Permit No. 7165 to Adams Morgan Hotel Owner LLC to construct and operate a 505 kWe emergency generator set powered by a 563 kWm diesel-fired engine at the property located at 1770 Euclid Street NW, Washington, DC 20009. The contact person for facility is Steve Harloe, Director, Development, at (703) 302-0057or [email protected].

Emissions:

Maximum emissions from the emergency generator set, operating five hundred (500) hours per year, are expected to be as follows:

Pollutant

Maximum Annual Emissions (tons/yr)

Total Particulate Matter (PM Total)

0.012

Sulfur Dioxide (SO2)

0.002

Nitrogen Oxides (NOx)

1.738

Volatile Organic Compounds (VOC)

0.037

Carbon Monoxide (CO)

0.186

The proposed emission limits for the equipment are as follows:

a.   Emissions from this unit shall not exceed those in the following table as measured according to the procedures set forth in 40 CFR 89, Subpart E for NMHC, NOx, and CO and 40 CFR 89.112(c) for PM. [40 CFR 60.4205(b), 40 CFR 60.4202(a)(2) and 40 CFR 89.112(a)-(c)]:

Pollutant Emission Limits (g/kW-hr)

NMHC+NOx

CO

PM

6.4

3.5

0.20

b.   Visible emissions shall not be emitted into the outdoor atmosphere from this generator, except that discharges not exceeding forty percent (40%) opacity (unaveraged) shall be permitted for two (2) minutes in any sixty (60) minute period and for an aggregate of twelve (12) minutes in any twenty-four hour (24 hr.) period during start-up, cleaning, adjustment of combustion controls, or malfunction of the equipment [20 DCMR 606.1].

c.   In addition to Condition II(b) exhaust opacity, measured and calculated as set forth in 40 CFR 86, Subpart I, shall not exceed [40 CFR 60.4205(b), 40 CFR 60.4202(a), and 40 CFR 89.113]:

1.   20 percent during the acceleration mode;

2.   15 percent during the lugging mode;

3.   40 percent during the peaks in either the acceleration or lugging modes. Note that this condition is streamlined with the requirements of 20 DCMR 606.1.

d.   An emission into the atmosphere of odorous or other air pollutants from any source in any quantity and of any characteristic, and duration which is, or is likely to be injurious to the public health or welfare, or which interferes with the reasonable enjoyment of life or property is prohibited. [20 DCMR 903.1]

The permit application and supporting documentation, along with the draft permit are available for public inspection at AQD and copies may be made available between the hours of 8:15 A.M. and 4:45 P.M. Monday through Friday. Interested parties wishing to view these documents should provide their names, addresses, telephone numbers and affiliation, if any, to Stephen Ours at (202) 535-1747.

Interested persons may submit written comments or may request a hearing on this subject within 30 days of publication of this notice.  The written comments must also include the person’s name, telephone number, affiliation, if any, mailing address and a statement outlining the air quality issues in dispute and any facts underscoring those air quality issues.  All relevant comments will be considered in issuing the final permit.

Comments on the proposed permit and any request for a public hearing should be addressed to:

Stephen S. Ours
Chief, Permitting Branch - Air Quality Division

Department of Energy and Environment
1200 First Street NE, 5th Floor
Washington, DC 20002

[email protected]

No comments or hearing requests submitted after March 13, 2017 will be accepted.