PUBLIC NOTICE
Draft Air Quality Permits 6892-R1 through 6900-R1, United States Department of State, Operation of nine existing 6.0 MMBTU/hr natural gas-fired boilers at the 2201 C Street NW
Notice is hereby given that, pursuant to 20 DCMR §210, the Air Quality Division (AQD) of the Department of Energy and Environment (DOEE), located at 1200 First Street NE, 5th Floor, Washington, DC, intends to issue air quality permit Nos. 6892-R1 through 6900-R1 to the United States Department of State to operate nine 6.0 Million BTU per hour natural gas-fired boilers at 2201 C Street NW. The contact person for the applicant is Nicholas Carros, Sustainability Manager, at (202) 736-4705. The applicant’s mailing address is 2201 C Street NW, B2A61, Washington DC 20520.
Emissions:
Maximum annual emissions from the each of the nine units has been estimated to be as follows:
Potential to Emit from Each Boiler |
|
Pollutant |
Tons per Year |
Carbon Monoxide (CO) |
2.16 |
Oxides of Nitrogen (NOx) |
0.946 |
Total Particulate Matter (PM Total) |
0.196 |
Volatile Organic Compounds (VOC) |
0.142 |
Oxides of Sulfur (SOx) |
0.0155 |
*PM Total includes both filterable and condensable fractions.
Emissions Limits:
The proposed emission limits for the boilers are as follows:
-
- Emissions of criteria pollutants from each of the nine (9) boilers shall not exceed those specified in the following table [20 DCMR 201]:
Boiler Emission Limits |
|
Pollutant |
Short-Term Limit (lb/hr) |
Carbon Monoxide (CO) |
0.494 |
Oxides of Nitrogen (NOx) |
0.216 |
Total Particulate Matter (PM Total)* |
0.0447 |
Sulfur Dioxide (SO2) |
0.00353 |
*PM Total includes both filterable and condensable fractions.
b. Visible emissions shall not be emitted into the outdoor atmosphere from the boiler, except that discharges not exceeding forty percent (40%) opacity (unaveraged) shall be permitted for two (2) minutes in any sixty (60) minute period and for an aggregate of twelve (12) minutes in any twenty-four hour (24 hr.) period during start-up, cleaning, adjustment of combustion controls, or malfunction of the equipment [20 DCMR 606.1]
c. An emission into the atmosphere of odorous or other air pollutants from any source in any quantity and of any characteristic, and duration which is, or is likely to be injurious to the public health or welfare, or which interferes with the reasonable enjoyment of life or property is prohibited. [20 DCMR 903.1]
d. Particulate matter (PM) emissions from each of the nine (9) boilers shall not exceed 0.11 pound per million BTU. [20 DCMR 600.1]
e. NOx and CO emissions shall not exceed those achieved with the performance of annual combustion adjustments on each boiler. To show compliance with this condition, the Permittee shall, each calendar year, perform adjustments of the combustion processes of the boilers with the following characteristics [20 DCMR 805.1(a)(4) and 20 DCMR 805.8(a) and (b)]:
i. Inspection, adjustment, cleaning or replacement of fuel burning equipment, including the burners and moving parts necessary for proper operation as specified by the manufacturer;
ii. Inspection of the flame pattern or characteristics and adjustments necessary to minimize total emissions of NOx and, to the extent practicable, minimize emissions of CO;
iii. Inspection of the air-to-fuel ratio control system and adjustments necessary to ensure proper calibration and operation as specified by the manufacturer; and
iv. Adjustments shall be made such that the maximum emission rate for any contaminant does not exceed the maximum allowable emission rate as set forth in Condition II of this permit.
The permit applications and supporting documentation, along with the draft permits are available for public inspection at AQD and copies may be made available between the hours of 8:15 A.M. and 4:45 P.M. Monday through Friday. Interested parties wishing to view these documents should provide their names, addresses, telephone numbers and affiliation, if any, to Stephen S. Ours at (202) 535-1747.
Interested persons may submit written comments or may request a hearing on this subject within 30 days of publication of this notice. The written comments must also include the person’s name, telephone number, affiliation, if any, mailing address and a statement outlining the air quality issues in dispute and any facts underscoring those air quality issues. All relevant comments will be considered in issuing the final permit.
Comments on the proposed permit and any request for a public hearing should be addressed to:
Stephen S. Ours
Chief, Permitting Branch - Air Quality Division
Department of Energy and Environment
1200 First Street NE, 5th Floor
Washington, DC 20002
No comments or hearing requests submitted after June 24, 2019 will be accepted.