Proposed Air Quality Permit 6795 – New Cingular Wireless

PUBLIC NOTICE

Proposed Air Quality Permit 6795 – New Cingular Wireless PCS, LLC, dba AT&T Mobility, One 50 kW natural gas fired emergency generator set at 2900 Adams Mill Road NW

Notice is hereby given that, pursuant to 40 C.F.R. Part 51.161, and D.C. Official Code §2-505, the Air Quality Division (AQD) of the District Department of the Environment (DDOE), located at 1200 First Street NE, 5th Floor, Washington, DC, intends to issue Permit #6795 to New Cingular Wireless PCS, LLC, dba AT&T Mobility to construct and operate one natural gas fired emergency generator set, located in Washington, DC. The contact person for the facility is Barbara Walden, Manager, Environment, Health and Safety, at (925) 327-2532.

Emergency Generator to be Permitted

Equipment Location 

Address

Equipment Size

Manufacturer and Model

Permit No.

2900 Adams Mill Road, NW

Washington DC

2900 Adams Mill Road, NW

Washington DC 2009

50 kW generator; 80 HP engine

Generac Engine/

Generac Industrial

SG050 Generator

6795

The proposed emission limits are as follows:

a.   Emissions from this unit shall not exceed those in the following table [40 CFR 60.4233(d) and Subpart JJJJ, Table 1]:

Pollutant Emission Limits (g/HP-hr)

NOx+HC

CO

VOC

10.0

387

N/A

b.   Visible emissions shall not be emitted into the outdoor atmosphere from this generator, except that discharges not exceeding forty percent (40%) opacity (unaveraged) shall be permitted for two (2) minutes in any sixty (60) minute period and for an aggregate of twelve (12) minutes in any twenty-four hour (24 hr.) period during start-up, cleaning, adjustment of combustion controls, or malfunction of the equipment [20 DCMR 606.1].

c.   An emission into the atmosphere of odorous or other air pollutants from any source in any quantity and of any characteristic, and duration which is, or is likely to be injurious to the public health or welfare, or which interferes with the reasonable enjoyment of life or property is prohibited. [20 DCMR 903.1]

The estimated maximum emissions from the emergency generator are as follows:

Pollutant

Maximum Annual Emissions (tons/yr)

Carbon Monoxide (CO)

17.06

Oxides of Nitrogen (NOx)

0.44

Total Particulate Matter , PM (Total)

0.00

Sulfur Dioxide (SOx)

0.00

The application to construct and operate the emergency generator and the draft permit and supporting documents are available for public inspection at AQD and copies may be made available between the hours of 8:15 A.M. and 4:45 P.M. Monday through Friday.  Interested parties wishing to view these documents should provide their names, addresses, telephone numbers and affiliation, if any, to Stephen S. Ours at (202) 535-1747.

Interested persons may submit written comments or may request a hearing on this subject within 30 days of publication of this notice.  The written comments must also include the person’s name, telephone number, affiliation, if any, mailing address and a statement outlining the air quality issues in dispute and any facts underscoring those air quality issues.  All relevant comments will be considered in issuing the final permit.

Comments on the proposed permit and any request for a public hearing should be addressed to:

Stephen S. Ours   