Draft Air Quality Permit 7366, U.S. General Services Administration, White House Service Center, Operation of a 2,700 kWe diesel-fired emergency generator set at the Eisenhower Executive Office Building, 1650 17th Street NW, Washington DC

Notice is hereby given that, pursuant to 20 DCMR §210, the Air Quality Division (AQD) of the Department of Energy and Environment (DOEE), located at 1200 First Street NE, 5th Floor, Washington DC, proposes to issue an air quality permit (No. 7366) to the General Services Administration, White House Service Center, to operate one 2,700 kWeemergency generator set powered by a 4,060 bhp diesel engine at the Eisenhower Executive Office Building , located at 1650 17th St. NW, Washington, D.C. The contact person for the facility is Mohammed Alam, Director, White House Service Center, and he can be reached at (202)-395-2235 or [email protected]. 

Emissions:

The applicant has estimated that maximum potential emissions from the emergency generator set, operating four hundred fifty (450) hours per year, are:

Pollutant Potential Emissions (tons per year)
Total Particulate Matter (PM Total) 0.12
Sulfur Dioxide (SO2) 0.01
Oxides of Nitrogen (NOx) 23.16
Volatile Organic Compounds (VOC) 0.35
Carbon Monoxide (CO) 1.03

The proposed overall emission limits for the equipment are as follows:

a.  Emissions from the generator set shall not exceed those found in the following table as measured using the procedures set forth in 40 CFR 1039, Subpart F. [40 CFR 60.4205(a), Table 1 to Subpart IIII of Part 60]

Pollutant Emission Limits (g/kWm-hr)
HC NOx CO PM
1.3 9.2 11.4 0.54[JA3] 

b.  Visible emissions shall not be emitted into the outdoor atmosphere from this generator set, except that discharges not exceeding twenty-seven percent (27%) opacity (unaveraged) shall be permitted for two (2) minutes during any start-up, cleaning, adjustment of combustion or operational controls, or regeneration of emission control equipment [20 DCMR 606.1 and 606.2(d)].

c.  An emission into the atmosphere of odorous or other air pollutants from any source in any quantity and of any characteristic, and duration which is, or is likely to be injurious to the public health or welfare, or which interferes with the reasonable enjoyment of life or property is prohibited. [20 DCMR 903.1]

Violation of the requirements of this condition that occurs as a result of unavoidable malfunction, despite the conscientious employment of control practices, shall be an affirmative defense for which the owner or operator shall bear the burden of proof. A malfunction shall not be considered unavoidable if the owner or operator could have taken, but did not take, appropriate steps to eliminate the malfunction within a reasonable time, as determined by the Department. [20 DCMR 903.13(b)]

Note: This condition is District-enforceable only.     

The permit application and supporting documentation, along with the draft permit are available for public inspection at AQD and copies may be made available between the hours of 9:00 A.M. and 5:00 P.M. Monday through Friday, excluding holidays. Interested parties wishing to view these documents should provide their names, addresses, telephone numbers and affiliation, if any, to Stephen S. Ours at (202) 498-8143 or [email protected]. Copies of the draft permit and related technical support memorandum are also available in the attachments section below.

Interested persons may submit written comments or may request a hearing on this subject within 30 days of publication of this notice. The written comments must also include the person’s name, telephone number, affiliation, if any, mailing address and a statement outlining the air quality issues in dispute and any facts underscoring those air quality issues. All relevant comments will be considered in issuing the final permit.

Comments on the draft permit and any request for a public hearing should be addressed to:

Stephen S. Ours       
Chief, Permitting Branch - Air Quality Division

Department of Energy and Environment
1200 First Street NE, 5th Floor
Washington, DC 20002

[email protected]

No comments or hearing requests submitted after December 21, 2026 will be accepted.

For more information, please contact Stephen S. Ours at (202) 498-8143 or [email protected].