PUBLIC NOTICE
Draft Air Quality Permits 7464 through 7471, United States Air Force
Construction and operation of eight (8) identical 75 kWe diesel-fired non-emergency generator sets at
Joint Base Anacostia-Bolling, 20 MacDill Boulevard SW, Washington DC
Notice is hereby given that, pursuant to 20 DCMR § 210, the Air Quality Division (AQD) of the Department of Energy and Environment (DOEE), located at 1200 First Street NE, 5th Floor, Washington DC, proposes to issue permit Nos 7461 through 7471 to the United States Air Force to construct and operate eight (8) 75 kWe non-emergency generator sets, powered by a 129 kWm diesel-fired engines (listed below), located at Joint Base Anacostia-Bolling, 20 MacDill Blvd SW, Washington, DC. The contact person for the facility is Amberleigh Ray, Air Quality Program Manager, at 202-284-4609 or [email protected].
| Equipment Location | Unit ID | Generator (Engine) Size | Engine Model Number | Permit No. |
| National Guard Logistics Support Area | EG-LSA-1 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7464 |
| National Guard Logistics Support Area | EG-LSA-2 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7465 |
| National Guard Logistics Support Area | EG-LSA-3 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7466 |
| National Guard Logistics Support Area | EG-LSA-4 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7467 |
| National Guard Logistics Support Area | EG-LSA-5 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7468 |
| National Guard Logistics Support Area | EG-LSA-6 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7469 |
| National Guard Logistics Support Area | EG-LSA-7 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7470 |
| National Guard Logistics Support Area | EG-LSA-8 | 75 kWe (129 kWm) | Perkins 1204J-E44TTAG2 | 7471 |
The proposed emission limits are as follows:
a. Emissions from each generator engine shall not exceed those in the following table as tested pursuant to the applicable test methods in 40 CFR 1039, Subpart F [40 CFR 60.4200(a)(1)(i), 40 CFR 60.4200(a)(2)(i), 40 CFR 60.4201(a), 40 CFR 60.4204(b), 40 CFR 1039.101(a), (b), (d), and (e)]:
| Pollutant Emission Limits (g/kW-hr) | |||
Emission Standard Type | NOx | CO | NMHC | PM |
| Transient and Steady State Testing† | 0.40 | 3.5 | 0.19 | 0.01‡ |
| Not-to-Exceed | 0.60 | 4.4 | 0.29 | 0.02 |
† Based on information on the EPA Certificate of Conformity No. TPKXL04.4SU1-015 and the California Air Resources Board (CARB) Executive Order U-R-022-0433 for the engine family to which this engine belongs, this 129 kWm unit was certified to the more stringent 130 < kWm < 560 category rather than the less stringent 56 < kWm < 130. Thus, the standards in this table reflect the standards of the more stringent, larger category.
‡ A family emission limit (FEL) has been granted by the U.S. Environmental Protection Agency (EPA) for this unit pursuant to 40 CFR 1039.101(d) as noted on the Certificate of Conformity for this engine.
b. Visible emissions shall not be emitted into the outdoor atmosphere from the engines, except that discharges shall be permitted for two (2) minutes during any start-up, cleaning, adjustment of combustion or operational controls, or regeneration of emissions control equipment; provided, that such discharges shall not exceed twenty-seven percent (27%) opacity (unaveraged). [20 DCMR 606.1 and 606.2(d)]
- An emission into the atmosphere of odorous or other air pollutants from any source in any quantity and of any characteristic, and duration which is, or is likely to be injurious to the public health or welfare, or which interferes with the reasonable enjoyment of life or property is prohibited. [20 DCMR 903.1]
Violation of the requirements of this condition that occurs as a result of unavoidable malfunction, despite the conscientious employment of control practices, shall be an affirmative defense for which the owner or operator shall bear the burden of proof. A malfunction shall not be considered unavoidable if the owner or operator could have taken, but did not take, appropriate steps to eliminate the malfunction within a reasonable time, as determined by the Department. [20 DCMR 903.13(b)]
This condition is District enforceable only.
d. The Permittee shall comply with the requirements for crankcase emissions, adjustable parameters, prohibited controls, and defeat devices specified in 40 CFR 1039.115. [40 CFR 60.4201(a), 40 CFR 60.4204(b)]
The estimated maximum potential emissions from the generator sets are as follows:
The following table shows estimated maximum potential emissions from the generator sets. It should be noted that the emissions estimates are based on 8,760 hours per year of operation. To estimate worst case emissions, the allowable steady state emissions standards were used as emission factors (except oxides of sulfur). These values are substantially in excess of the certification testing values provided to EPA to justify engine certification. AP-42 emission factors were used to estimate SOx emissions.
| Pollutant | Potential Emissions from Each Engine (tons per year) | Potential Emission from All Eight Engines (tons per year) |
| Particulate Matter (PM) | 0.025 | 0.20 |
| Oxides of Sulfur (SOx) | 1.55 | 12.43 |
| Oxides of Nitrogen (NOx) | 0.498 | 3.99 |
| Volatile Organic Compounds (VOC) | 0.237 | 1.89 |
| Carbon Monoxide (CO) | 4.36 | 34.89 |
The permit application and supporting documentation, along with the draft permit are available for public inspection at AQD and copies may be made available between the hours of 9:00 A.M. and 5:00 P.M. Monday through Friday. Interested parties wishing to view these documents should provide their names, addresses, telephone numbers and affiliation, if any, to Stephen S. Ours at (202) 498-8143 or [email protected]. Copies of the draft permit and related technical support memorandum are also available in the attachments section below.
Interested persons may submit written comments or may request a hearing on this subject within 30 days of publication of this notice. The written comments must also include the person’s name, telephone number, affiliation, if any, mailing address and a statement outlining the air quality issues in dispute and any facts underscoring those air quality issues. All relevant comments will be considered before taking final action on the permit application.
Comments on the proposed permit and any request for a public hearing should be addressed to:
Stephen S. Ours
Chief, Permitting Branch - Air Quality Division
Department of Energy and Environment
1200 First Street NE, 5th Floor
Washington DC 20002
No comments or hearing requests submitted after November 23, 2026 will be accepted.